Açıklama
Code
YAVZ3V , NAYFGbY         AL/PVC/STA/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
Flat Steel Wire and Galvanized Steel Tape
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×5018,3479,610000,641153137
1×7020,2594,310000,443187173
1×9522,1725,710000,320223212
1×12023,4834,510000,253252247
1×15025,8998,710000,206280280
1×18528,11195,510000,164314321
1×24030,81444,25000,125358374
1×30034,31847,85000,100397426
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×1018,8728,910003,08
2×1620,8875,710001,91
2×2523,91132,210001,2010383
2×3525,91326,310000,868123101
2×5029,41623,510000,641145121
2×7033,82093,35000,443180155
2×9537,92606,65000,320216189
2×12040,83009,55000,253246220
2×15046,33763,85000,206276249
2×18551,04483,22500,164313287
2×24056,95536,52500,125362339
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×1019,7798,710003,08
3×1621,8967,010001,91
3×2525,21260,810001,2010383
3×3527,51487,010000,868123101
3×5031,21834,210000,641145121
3×7036,02372,45000,443180155
3×9540,42966,25000,320216189
3×12044,03496,05000,253246220
3×15049,54291,22500,206276249
3×18554,55125,02500,164313287
3×24060,96344,62500,125362339
3×30067,37836,92500,100415401
3×40075,59722,12500,0778474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+1023,01064,610001,91 – 3,08
3×25+1626,41378,610001,20 – 1,9110383
3×35+1628,41594,710000,868 – 1,91123101
3×50+2533,02027,210000,641 – 1,20145121
3×70+3537,32565,95000,443 – 0,868180155
3×95+5042,13188,15000,320 – 0,641216189
3×120+7046,33840,55000,253 – 0,443246220
3×150+7051,04538,65000,206 – 0,443276249
3×185+9556,85579,72500,164 – 0,320313287
3×240+12062,76771,32500,125 – 0,253362339
3×300+15069,78395,42500,100 – 0,206415401
3×400+18578,010496,72500,0778 – 0,164474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×1021,2892,810003,08
4×1623,61095,310001,91
4×2527,51449,710001,2010383
4×3530,11741,410000,868123101
4×5034,72198,810000,641145121
4×7039,62802,15000,443180155
4×9544,93580,55000,320216189
4×12048,44165,95000,253246220
4×15054,65127,22500,206276249
4×18560,66256,32500,164313287
4×24067,37671,32500,125362339
4×30075,09653,32500,100415401
4×40083,712015,02500,0778474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×1022,81069,210003,08
5×1625,51327,410001,91
5×2529,91799,410001,2010383
5×3533,32219,010000,868123101
5×5038,02760,55000,641145121
5×7043,43573,15000,443180155
5×9549,34554,75000,320216189
5×12053,25349,62500,253246220
5×15060,66700,92500,206276249
5×18566,88103,42500,164313287
5×24074,710110,82500,125362339
5×30082,712572,22500,100415401
5×40092,915867,02500,0778474468
Note :
Current carrying capacities are valid at 30°C ambient temperature