Açıklama

tds

Code
YAVCV , NAYCY              AL/PVC/ SC/PVC
Voltage Rating
0.6/1 kV
Standards
TS IEC 60502-1 , VDE 0276
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Stranded Aluminum Conductor (Class 2)
Insulation
PVC (Polyvinyl Chloride)
Filler
PVC Filler
Armour
Copper Wire and Copper Tape
Sheath
PVC (Polyvinyl Chloride)
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:15D ( D : Overall Diameter )
Test Voltage:3,5 kV
Application:
For installation indoors and outdoors, in cable ducts, underground , in power or switching stations, local energy distribution
industrial plants, where there is no risk of mechanical damage.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×10/1012,4300,010003,08 – 1,83
1×16/1614,2398,610001,91 – 1,15
1×16/1013,4339,410001,91 – 1,83
1×25/1615,8468,610001,20 – 1,1510891
1×35/1616,8523,410000,868 – 1,15129112
1×50/2518,5655,910000,641 – 0,727153137
1×70/3520,4860,010000,443 – 0,524187173
1×95/5022,61087,910000,320 – 0,387223212
1×120/7026,41540,710000,253 – 0,268252247
1×150/7029,01733,410000,206 – 0,268280280
1×185/9531,92192,410000,164 – 0,193314321
1×240/12035,12704,55000,125 – 0,153358374
1×300/15041,73651,35000,100 – 0,124397426
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
2×10/1018,1563,510003,08 – 1,83
2×16/1020,1680,010001,91 – 1,83
2×25/1624,0962,010001,20 – 1,1510383
2×35/1626,11127,810000,868 – 1,15123101
2×50/2529,61461,910000,641 – 0,727145121
2×70/3534,01938,05000,443 – 0,524180155
2×95/5038,52552,05000,320 – 0,387216189
2×120/7041,93132,15000,253 – 0,268246220
2×150/7047,43836,45000,206 – 0,268276249
2×185/9552,64797,42500,164 – 0,193313287
2×240/12058,96043,12500,125 – 0,153362339
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×10/1019,0617,610003,08 – 1,83
3×16/1021,1753,010001,91 – 1,83
3×25/1625,31069,610001,20 – 1,1510383
3×35/1627,61264,810000,868 – 1,15123101
3×50/2531,51648,410000,641 – 0,727145121
3×70/3536,22228,55000,443 – 0,524180155
3×95/5041,02878,95000,320 – 0,387216189
3×120/7044,63527,45000,253 – 0,268246220
3×150/7050,64322,82500,206 – 0,268276249
3×185/9556,15396,02500,164 – 0,193313287
3×240/12062,96803,22500,125 – 0,153362339
3×300/15069,88516,12500,100 – 0,124415401
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
3×16+10/1022,3831,710001,91 – 3,08 – 1,83
3×25+16/1626,51169,410001,20 – 1,91 – 1,1510383
3×35+16/1628,51360,110000,868 – 1,91 – 1,15123101
3×50+25/2532,81781,010000,641 – 1,20 – 0,727145121
3×70+35/3537,52406,45000,443 – 0,868 – 0,524180155
3×95+50/5042,63080,05000,320 – 0,641 – 0,387216189
3×120+70/7047,43924,55000,253 – 0,443 – 0,268246220
3×150+70/7052,04550,02500,206 – 0,443 – 0,268276249
3×185+95/9558,45793,02500,164 – 0,320 – 0,193313287
3×240+120/12064,77209,42500,125 – 0,253 – 0,153362339
3×300+150/15072,19049,82500,100 – 0,206 – 0,124415401
3×400+185/18581,111487,22500,0778 – 0,164 – 0,0991474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
4×10/1020,5709,010003,08 – 1,83
4×16/1623,7947,810001,91 – 1,15
4×25/1627,61248,710001,20 – 1,1510383
4×35/1630,21507,710000,868 -1,15123101
4×50/2534,91996,810000,641 – 0,727145121
4×70/3539,82643,95000,443 – 0,524180155
4×95/5045,53419,45000,320 – 0,387216189
4×120/7049,54261,25000,253 – 0,268246220
4×150/7055,75169,92500,206 – 0,268276249
4×185/9562,26507,82500,164 – 0,193313287
4×240/12069,38111,92500,125 – 0,153362339
4×300/15077,410317,42500,100 – 0,124415401
4×400/18586,813020,52500,0778 – 0,0991474468
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
5×10/1022,1823,810003,08 – 1,83
5×16/1625,51101,510001,91 – 1,15
5×25/1630,01485,710001,20 – 1,1510383
5×35/1633,41841,110000,868 – 1,15123101
5×50/2538,22378,55000,641 – 0,727145121
5×70/3543,63172,35000,443 – 0,524180155
5×95/5049,94158,35000,320 – 0,387216189
5×120/7054,35044,42500,253 – 0,268246220
5×150/7061,66259,52500,206 – 0,268276249
5×185/9568,47760,62500,164 – 0,193313287
5×240/12076,79764,22500,125 – 0,153362339
5×300/15085,212308,72500,100 – 0,124415401
5×400/18596,015705,32500,0778 – 0,0991474468
Note :
Current carrying capacities are valid at 30°C ambient temperature.