Açıklama

tds

Code
H05V-U , H07V-U     CU/PVC
Voltage Rating
300/500 V , 450/750 V
Standards
EN 50525-2-31 / VDE 0281 / IEC 60227-3 / BS 6004
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Solid Copper Conductor (Class 1)
Insulation – izolasyon
PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
Technical Data
Max. Operating Temperature:70°C
Short  Circuit  Temperature:160°C (max.5 sec.)
Bending Radius:12D ( D : Overall Diameter )
Test Voltage:2 kV, 2,5 kV
Application
In dry rooms, switch and distribution boards, for laying in conduit on and under plaster and
on insulating supports above plaster
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Conduit at 20°CIn Air at 30°C
1×0,50*2,09,010036,012
1×0,75*2,211,310024,515
1×1*2,314,310018,11119
1×1,52,820,010012,114,524
1×2,53,332,01007,4119,532
1×43,845,81004,612642
1×64,365,01003,083454
Note 1:
* For H05V-U Cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature
1×105,91101001,834673