Açıklama

tds

Code
H05V2-K , H07V2-K        CU/PVC
Voltage Rating
300/500 V , 450/750 V
Standards
EN 50525-2-31 , VDE 0281 , IEC 60227 , BS 6004
IEC 60228Conductor
Reaction to Fire Classification ( CPR )
EN 60332-1-2Flame Retardant
Conductor
Flexible Copper Conductor (Class 5)
Insulation
Heat Resistance PVC (Polyvinyl Chloride)
Filler
Armour
Sheath
Technical Data
Max. Operating Temperature:90°C
Short  Circuit  Temperature:160°C (max.5 sec)
Bending Radius:6D ( D : Overall Diameter )
Test Voltage:2 kV , 2,5 kV
Application
When its required high operating temperatures (90°C) and for house hold appliances. It used as surface mounted or flush mounted
in stationary plants. Dry places, distribution boards and closed spaces, factories workshops and kind of work places.
Nominal Cross SectionOverall DiameterNet WeightDelivery LengthResistance at 20°CCurrent Carrying Capacity
(mm²)(mm)(kg/km)(m)(ohm/km)In Ground at 20°CIn Air at 30°C
1×0,50*2,18,110039,0 –12
1×0,75*2,310,810026,0 –15
1×1*2,413,810019,51119
1×1,52,920,610013,314,524
1×2,53,532,61007,9819,532
1×44,046,91004,952642
1×64,667,31003,303454
1×105,9110,91001,914673
1×166,9164,61001,216198
1×258,6271,410000,78080129
1×359,7373,610000,55499158
1×5011,5523,510000,386119198
1×7013,1714,210000,272151245
1×9515,2949,310000,206182292
1×12016,71169,510000,161210344
1×15018,71462,410000,129240391
1×18521,01871,910000,106273448
1×24023,52348,410000,0801320528
1×30026,22952,310000,0641608
1×40030,03994,710000,0486726
1×50034,15139,210000,0384830
Note 1:
* For H05V2-K cables
Note 2:
Current carrying capacities are valid at 30°C ambient temperature